====== How to flush the Coils====== ===== Preperation ===== Before you start to the procedure you should get everything together, that is needed. === You need === * Vinegar essence * Destilled Water * Boxes (I recommend at least two) * Submersible pump * Power supply * Blind plugs 2x * Spanner (19, 17 & 14) * Some paper ===== Getting started ===== - Turn off the pump and chiller. - Make some space where the bigger pipe is split for the upper and lower coils (underneath the S-MOT Laser-System). - Put a box there and remove the big pipes from the Tee. Do this above the box, since the water will start to drain out of the big pipes. - Close the big pipes using the blind plugs. - Connect the pump to the Input-Tee (labels are on the smaller pipes). - Put the pump into a box with water (you can use tap water) and vinegar essence (I used a quarter of a bootle). - Fix the Outut-Tee so that the water will drip into the box again. - Connect the pump to the Power supply (check that the voltage is reduced to zero). - Now slowly increase the Voltage until the water starts to drip out of the Output-Tee. Increasing the voltage too fast will cause the pump not to work. - If the water starts to circulate you can increase the Voltage to max 12V. - Flush the coils for a couple of hours - When you are done with flushing the coils you have to flush the coils with destilled water, to remove all residuals of the vinegar-water-mix (flush it with ~5 litres NOT CIRCULATING)